Most electrical faults announce themselves. A breaker trips, a GFCI won't reset, something smells hot. A lost neutral doesn't. The power stays on, and the first sign of trouble is often a string of dead electronics.
From two independent circuits to one voltage divider
In a normal, properly grounded split-phase system (covered in our guide to why North America runs 120/240V), each 120V leg has its own reference back to a solid, grounded neutral. Both legs are pinned to the same fixed zero, so the load on one has no effect on the other.
Now say the neutral breaks somewhere between the panel and the utility transformer (a corroded lug, a damaged connection at the meter) while both hot legs stay intact. The legs are then no longer independent. The 120V loads on each leg stop behaving like two separate circuits and start behaving like one series circuit stretched across the full 240V. With the neutral connected, each leg's loads sit in parallel, each pinned to the same fixed reference. With the neutral open, they become a voltage divider. The leg carrying the lighter load takes a bigger share of the 240V, and the heavier leg gets less. You might read 160V and 80V instead of an even 120V and 120V. The exact split depends on how unevenly the loads happen to be divided at that moment.
Phase-to-phase voltage stays at a solid 240V through all of this. That reading is taken straight across the transformer winding and never touches the neutral. So the reading most people would check first looks normal, which is why this fault is easy to miss unless you test for it specifically.
Equipment damage, shock and fire
Most of the equipment damage happens on the overvoltage side. Lights, electronics and appliance control boards on the lightly loaded leg can see well above their rated 120V, and in a bad imbalance it can approach the full 240V. Sustained overvoltage like that damages components that were never built for it. The undervoltage side just seems a little weak: dim lights, a motor that struggles. That's easy to dismiss as an annoyance, but it is the same fault.
An open service neutral is also a shock and fire hazard. With the service neutral open, return current takes any other available path back to the transformer: the grounding electrode, the water pipe, the gas pipe, the cable or telephone bond. That can put a dangerous voltage on metal that is supposed to sit at zero, meaning pipes, faucets and appliance cases. It also pushes current through bonding conductors that were never sized to carry it, which can start a fire. Treat a suspected open service neutral as a shock and fire hazard first. Get the power off at the meter instead of troubleshooting it live.
Sources
- National Electrical Code, Article 200 (use and identification of grounded conductors) and 300.13(B) (continuity of the grounded conductor in multiwire branch circuits), on the role of a continuous neutral connection.
- Mike Holt's Electrical Forum, discussion threads on open and lost neutral conditions and the resulting voltage-divider behavior between unbalanced 120V legs, professional trade community discussion, presented here as such rather than a formal study.
This is general educational information, not a substitute for an in-person evaluation of your specific electrical system by a licensed electrician. If you suspect a lost neutral, an unusual mix of dim and overly bright lights, or electronics failing without an obvious cause, treat it as urgent and have it evaluated promptly.
You're welcome to quote this article elsewhere with attribution and a link back to the original at hancoelectric.com.