What size electrical service does this house need?

A full NEC load calculation, starting from nothing. Square footage, the appliances, the heating, and anything you plan to add.

Which calculation this is. The optional method for a dwelling unit, NEC Article 220.82. It sizes a service that does not exist yet. If instead you are adding one thing to a service you already have, the EV charger and heat pump calculators use the existing dwelling method, NEC 220.83, which is the one an inspector will expect for that job.

Important disclaimer. This calculator is provided for general estimation purposes only and does not constitute professional electrical advice, engineering analysis, or a code compliance determination. Results are based on what you enter, under the NEC Article 220.82 optional method for the code edition you select. Actual loads, service sizing requirements and upgrade needs vary with specific appliance nameplate ratings, utility requirements, local amendments to the NEC, physical inspection of existing wiring, and other site conditions this tool cannot assess. No electrical work should be planned, permitted, or performed based solely on the results of this calculator. Hanco Electric LLC assumes no liability for decisions made from this output. Always consult a licensed electrician for a proper load calculation and an on-site evaluation.

Before you start

Use nameplate ratings wherever you have them. The optional method counts appliances at their full nameplate value, so a real number beats a good guess every time. Where you do not have one, there is an estimate option and the result will tell you which figures were estimated.

One thing worth knowing up front. The optional method does not use the range and dryer demand tables. Under 220.82 a range counts at its full nameplate rating, not the reduced Table 220.55 figure, and there is no 5,000 VA dryer minimum. That is why this calculation can come out differently from one done the standard way, and both are correct.

1. Which code edition

Washington adopts the 2026 NEC on 31 December 2026. Three things change for this calculation, and all three pull in different directions, so it is worth running both if your work lands near that date. The general lighting load drops from 3 to 2 VA per square foot, the first demand tier drops from 10 kVA to 8 kVA, and EV charging equipment moves out of the demand tiers into its own part at 100 percent.

2. The house

Each kitchen carries two small appliance circuits at 1,500 VA each, so a second kitchen adds 3,000 VA before a single appliance is counted. An ADU or a mother-in-law unit with its own cooking counts. A wet bar usually does not.
1,500 VA each. Nearly every house has one. Enter 0 only if there is genuinely no laundry circuit.

3. The big appliances

Gas appliances draw nothing electrically, so a house on a gas range has more room than the same house all electric. Enter these at full nameplate. Under the optional method the range is not reduced by Table 220.55 and the dryer has no minimum.

4. Kitchen appliances

The two small appliance circuits already cover whatever is plugged into them. An appliance only counts separately if it is built in, hardwired, or on its own breaker. A countertop microwave on a kitchen outlet is already counted. An over-the-range one is not. If you are unsure, check it anyway: that is the cautious side and it will not undersize you.

5. Heating and cooling

Heating and cooling never run at the same time, so the code counts only the larger of the two. Article 220.82(C) compares six different ways of working out that figure and takes whichever is biggest, so entering everything you have is safe.

Air conditioning

Only for a separate cooling unit. A heat pump is one machine that both heats and cools, so do not enter it twice.

6. EV charging

7. Anything else

Sauna, pool or well pump, shop subpanel, welder, second panel. Anything fastened in place or permanently connected that the lists above missed. Use the nameplate figure rather than an estimate of what you think it draws. Leave heating and cooling out of this section, since section 5 already has them.

This is a planning estimate from Hanco Electric, based on what you entered and on the code edition selected. It is not a design, not a permit submittal, and not a substitute for a licensed electrician evaluating the installation on site. The authority having jurisdiction has the final say on any load calculation.